ProServe Fire Protection provides complete fire safety equipment installation, inspection and testing, maintenance and repair services to properties in Cary, NC and the surrounding areas.

We are available 24 hours a day to meet your fire protection needs. Read our reviews and find out why ProServe Fire is considered to be the best fire protection company in the Cary, NC area.

Local Reviews
for Cary, NC

ProServe Fire Protection Rated 4.8 out of 5 stars based on 6 customer reviews
Mobile Tools for Contractors and Service Professionals Powered by Nearby Now

Our Reviews by City



Manager




Review of ProServe Fire Protection


Great service!




Review of ProServe Fire Protection

Always great service! highly recommend


review




Review of ProServe Fire Protection


Awesome service




Review of ProServe Fire Protection

Great service guy. Easiest fire service ever.


Good Service




Review of ProServe Fire Protection

Service tech was on time, polite, efficient, No complaints.


Great Service




Review of ProServe Fire Protection

The tech was very friendly and experienced.


Jacob  S.

Jacob S.

Fire Suppression and Access Control Installation Pull Permits Pick up 1" gas valve at shop and Deliver 1" gas valve to location Install new 9.0 gallon Ansul system Perform final acceptance testing site survey for upcoming fire system installation. Meet Clay onsite at 1:30pm to walk off job with customer Kevin Lee. If asked about 1" gas valve, it has been ordered and will arrive on Friday. Day 3 continue installation

Near Sembler Ln, Cary, NC 27519
Joey J.

Joey J.

Emergency / Exit Lights and Portable Extinguishers Service Call fm stopped by location needs lights inspected and fixed MUST COLLECT PAYMENT AT THE TIME OF SERVICE FOR THIS APPOINTMENT. PC1 Pricing unless otherwise posted Can take a VISA/MC/AMEX/DSCR, check or cash. Perform the Annual Portable Fire Extinguisher Inspection as per NFPA 10. Any maintenance services or new units required must be documented and customer authorization obtained before work can be performed. Inoperable Deficiency: One emergency light failed 30 second test with new battery. Inoperable Deficiency: One emergency light failed the 30 second test with a new battery Inoperable Deficiency: One emergency light failed the 30 second test with a new battery

Near Darrington Dr, Cary, NC 27513
Joey J.

Joey J.

Portable Extinguishers Inspection Perform the Annual Portable Fire Extinguisher Inspection as per NFPA 10. Any maintenance services or new units required must be documented and customer authorization obtained before work can be performed.

Near Kildaire Park Dr, Cary, NC 27518
Joey J.

Joey J.

S2012154046 Initial Service(s) Performed: Annual Emergency Exit Light Inspection per NFPA 101 Deficiencies Identified: One exit light needs a new 6.8v600ma nicad battery Scope of Work: Definitions of what each line item listed service below is as follows: Replace (1) 6.8v 600mah battery batteries. -The emergency lighting system shall be arranged and maintained to provide the required illumination automatically in the event of any interruption of normal lighting. Exclusions: Electrical and /or Plumbing work (if required). Permits (if required). Any changes mandated as a result of an Authority Having Jurisdiction (AHJ) review of the proposed scope of work. Emergency / Exit Lights Repair S2012154046 Initial Service(s) Performed: Annual Emergency Exit Light Inspection per NFPA 101 Deficiencies Identified: One exit light needs a new 6.8v600ma nicad battery Scope of Work: Definitions of what each line item listed service below is as follows: Replace (1) 6.8v 600mah battery batteries

Near Walnut St, Cary, NC 27518
Joey J.

Joey J.

Portable Extinguishers and Emergency / Exit Lights Priority Inspection Perform the Annual Portable Fire Extinguisher Inspection as per NFPA 10. Any maintenance services or new units required must be documented and customer authorization obtained before work can be performed. Luis called to ask for a ext inspection, also while on site all of his exit lights are out, he would like these fixed.

Near SW Cary Pkwy, Cary, NC 27513
Joey J.

Joey J.

Tech Clock IN/OUT IVR 844-347-3487 286092 Emergency / Exit Lights and Portable Extinguishers Inspection Conduct 30 sec.Annual Push Button test on all Emerg/Exit lights throughout location Conduct annual inspection on all extinguishers throughout location as required per NFPA10 and any other applicable codes/standards (review all areas with site manager).

Near Renaissance Park Pl, Cary, NC 27513
Jacob  S.

Jacob S.

Portable Extinguishers Inspection Perform Annual Fire Extinguisher Inspection as per NFPA 10 MUST COLLECT PAYMENT AT THE TIME OF SERVICE FOR THIS APPOINTMENT. PC1 Pricing unless otherwise posted Can take a VISA/MC/AMEX/DSCR, check or cash.

Near Kildaire Farm Rd, Cary, NC 27518
Jacob  S.

Jacob S.

Tech Clock IN/OUT IVR 844-347-3487 286415 Emergency / Exit Lights and Portable Extinguishers Inspection Conduct 30 sec.Annual Push Button test on all Emerg/Exit lights throughout location Conduct annual inspection on all extinguishers throughout location as required per NFPA10 and any other applicable codes/standards (review all areas with site manager).

Near Kildaire Farm Rd, Cary, NC 27518
Jacob  S.

Jacob S.

Extinguisher Inspection Annual Emergency & Exit Light Inspection Annual IVR Process: Please call Service Channel at 516-500-7776 or use the mobile Service Channel GPS app. Use Pin # 1388023 and the PO # above on Work Order to Check In and Out. Call 833-675-4305 before leaving Center if any deficiencies are found. Pictures of deficiencies are required for payment. All jobs must be scheduled directly with the KinderCare facility. The Center Director must sign the bottom of the work order and your Technician must utilize the IVR to check in and out for this work to be considered complete. If tech finds that the center is Temporarily Closed Do Not Leave - Call 833-675-4305 to get the Lockbox Code to the center so inspection can be completed. After putting systems on test, all Technicians must contact Century Fire Protection, 833-675-4305, to receive confirmation the system is on test. Any questions regarding passwords can also be directed to the same number. “Completed inspection forms are

Near Laura Duncan Rd, Cary, NC 27513
Jacob  S.

Jacob S.

Fire Suppression Inspection Ansul R102 3 gallon Left end of cabinet hood: Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur. Deficiency for Ansul R102 3 gallon Left end of cabinet hood: small portable fryer not covered by suppression nozzles, need to be piped into suppression system.

Near Kildaire Farm Rd, Cary, NC 27511
Jacob  S.

Jacob S.

Fire Suppression Installation Submit plans to town of Cary Modify existing fire system to protect new appliance layout underneath original hood as well new 6" hood added. Perform final acceptance testing Site survey to determine existing hood dimensions, system details and appliance layout to include new hood to be installed. Call scott from onsite. deactivate fire system

Near E Cedar St, Cary, NC 27511
Jacob  S.

Jacob S.

Fire Suppression Inspection Ansul R102 6 Gallon Back Hood RIght End Cabinet: Blow off caps are not authorized to be installed at this account unless found missing from nozzle. Ansul R102 6 Gallon Back Hood RIght End Cabinet: Semi-Annual Kitchen Suppression System Inspection

Near Columbus Ave, Cary, NC 27518
Jacob  S.

Jacob S.

Fire Suppression Inspection Ansul R-102 3.0 Right Side of the Hood: Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur. Deficiency for Ansul R-102 3.0 Right Side of the Hood: 3.0 gallon tank due for 12 year hydro static testing, along with 101-20 C02 cartridge replacement and regulator test

Near Caitboo Ave, Cary, NC 27518
Matthew M.

Matthew M.

Tech Clock IN/OUT IVR 844-347-3487 278821 Fire Suppression Inspection

Near Winston Hill Dr, Cary, NC 27513
Jacob  S.

Jacob S.

Fire Suppression Inspection Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur. Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur. MUST COLLECT PAYMENT AT THE TIME OF SERVICE FOR THIS APPOINTMENT. PC1 pricing unless otherwise posted VISA/MC/AMEX/DSCR, check or cash. Ryan said that there was something wrong with suppression system (above the filters

Near SW Cary Pkwy, Cary, NC 27513
Jacob  S.

Jacob S.

Fire Suppression Inspection MUST COLLECT PAY AT TIME on this account. PC-1 pricing. Pyro Chem PCL 4.6 Gallon Left End Of Hood: Perform the Semi-Annual Kitchen Hood Fire Suppression System Inspection as per NFPA 17

Near Tryon Rd, Cary, NC 27518
Jacob  S.

Jacob S.

Tech Clock IN/OUT IVR 844-347-3487 300054 Portable Extinguishers Service Call 3 extinguishers need to be recharged. In office by emergency exit door, emergency door in Housewares Department, and in Women's Active/Seasonal

Near Walnut St, Cary, NC 27518
Jacob  S.

Jacob S.

Fire Suppression Inspection Pyro Chem PCL 460 460 Right Of Hood: Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur. MUST COLLECT PAYMENT AT THE TIME OF SERVICE at this appointment. See comments for pricing. Can take a VISA/MC/AMEX, check or cash. Ansul R102 6 Gallon End Of Hood: Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test. If unable to disarm alarm or place on test document same on inspection report as reason why full function test did not occur.

Near E Chatham St, Cary, NC 27511
Jacob  S.

Jacob S.

Detection failed in May Portable Extinguishers, Emergency / Exit Lights, and Fire Suppression Inspection Perform the Annual Portable Fire Extinguisher Inspection as per NFPA 10. Any maintenance services or new units required must be documented and customer authorization obtained before work can be performed. (Quick Check) Perform the Annual Emergency/Exit Light Inspection to each unit on-site. No certification label is to be applied for this type of inspection. Additional maintenance needed i.e.batteries and bulbs must have customer approval. Any units that require replacement must be documented as a deficiency and installed on an approved return trip, if same day approval is not obtained. Ansul r102 6 gallon right side of hood: Semi-Annual Kitchen Suppression System Inspection as per NFPA 17A. Fire Alarm system (if present) must be placed on test prior to performing service. Access to FACP for purpose of reset must be made available prior to conducting full function test.

Near Cary Towne Blvd, Cary, NC 27511
Jacob  S.

Jacob S.

Tech Clock IN/OUT IVR 844-347-3487 171078 Emergency / Exit Lights and Portable Extinguishers Inspection Conduct 30 sec. Annual Push Button test on all Emerg/Exit lights throughout location Conduct annual inspection on all extinguishers throughout location as required per NFPA10 and any other applicable codes/standards (review all areas with site manager).

Near Green Level Church Road, Cary, NC 27519
Jacob  S.

Jacob S.

Semi-Annual Kitchen Suppression Inspection IVR Process: Please call Service Channel at 516-500-7776 or use the mobile Service Channel GPS app. Use Pin # 1388023 and the PO # above on Work Order to Check In and Out. Call 833-675-4305 before leaving location if any deficiencies are found. All jobs must be scheduled facility directly. The location director or manager must sign the bottom of the work order and your Technician must utilize the IVR to check in and out for this work to be considered complete. Once complete, send the completed work order and invoice to century360@centuryfp.com for processing. After putting systems on test, all Technicians must contact Century Fire Protection, 833-675-4305, to receive confirmation the system is on test. Any questions regarding passwords can also be directed to the same number. Fire Suppression Inspection Semi-Annual Kitchen Suppression Inspection

Near Walnut St, Cary, NC 27511
Richard H.

Richard H.

Near Lord Dr, Cary, NC 27511
Richard H.

Richard H.

Near Residents Club Dr, Cary, NC 27519
Jacob  S.

Jacob S.

Portable Extinguishers Inspection Perform Annual Fire Extinguisher Inspection as per NFPA 10 Collect Pay at Time on this account. See comments for pricing. If they refuse proceed unless new equipment has to be installed.

Near Green Level Church Road, Cary, NC 27519
Jacob  S.

Jacob S.

Portable Extinguishers and Fire Suppression Inspection Perform the Annual Portable Fire Extinguisher Inspection as per NFPA 10. Any maintenance services or new units required must be documented and customer authorization obtained before work can be performed. MUST COLLECT PAYMENT AT THE TIME OF SERVICE FOR THIS APPOINTMENT. See comments for pricing. If pricing not posted contact office! Can take a VISA/MC/AMEX, check or cash. Obtain/verify contact information: corporate or billing address if different from location, the Name of manager/owner/scheduler, EMAIL ADDRESS, Best contact Phone Number, Fax number if available. Note all information in a comment on the location. Ansul R-102 6 Gallon Right Side End Cabinet: Perform semi annual kitchen suppression system inspection MUST COLLECT PAYMENT AT THE TIME OF SERVICE FOR THIS APPOINTMENT. PC1 pricing unless otherwise posted VISA/MC/AMEX/DSCR, check or cash. Suggested for Ansul R-102 6 Gallon Right Side End Cabinet: Excessive grease bui

Near Green Level Church Road, Cary, NC 27519